Think tank Energy Innovation proposes a faster, cheaper, and cleaner route for powering off-grid data centers: giant heat batteries that are fueled by low-cost solar and wind.

  • Wildmimic@anarchist.nexus
    link
    fedilink
    English
    arrow-up
    1
    ·
    edit-2
    6 hours ago

    we have a refrigeration cycle that enables concentrating moving heat. using the heat generated to feed it into thermal batteries will not be enough on it’s own, but it could provide additional efficiency.

    Edit: I just realized my thinking error. Can only provide a base temperature. Better than nothing tho!

    • Womble@piefed.world
      link
      fedilink
      English
      arrow-up
      1
      ·
      edit-2
      6 hours ago

      In order to move heat from the colder side at the computer to the hotter side at the battery it would be slow and would have to expend energy to move it.

      Right, but those refrigeration cycles take energy to run themselves, and by design slow down the flow of heat away from the computers you are trying to cool.

      It is possible you could somewhat* decrease the amount of fresh electricity used if you massively overbuilt you cooling to include incredibly inefficient active cooling pushing heat from the computers to a battery 2 or 3 times it’s temperature. But the whole concept of a battery making sense relies upon cheap power for part of the day and much less the other part of the day (e.g. solar). Why would you want to massively overspend on cooling in order to use less of the abundant intermittent power you want to take advantage of?

      * the difference in efficiency between using a heat pump to push heat into your battery from a coolant outflow at 100 degrees and one from outside at 0 degrees is only about 10%