    Put the temp sensor on a separate system from the controls

    • bluefishcanteen@sh.itjust.works
      link
      fedilink
      English
      arrow-up
      5
      ·
      3 days ago

      100% this. I work in pharma, that’s how we do it. You would use a separate system for monitoring - the plus side being is that monitoring would likely use a thermocouple which should give you better accuracy. Having an independent system also means that you can move the temperature monitoring device to wherever the “hot spot” in your freezer is based on the mapping that you should be doing.

      • boonhet@lemmy.zip
        link
        fedilink
        English
        arrow-up
        1
        ·
        3 days ago

        Temperature policy changes? So you don’t have to send a tech to each location.

        • Steve@startrek.website
          link
          fedilink
          English
          arrow-up
          1
          ·
          edit-2
          3 days ago

          Then you get what we have here. Shouldnt there be an employee at each location with a button pushing finger?

      • hanke@feddit.nu
        link
        fedilink
        English
        arrow-up
        5
        arrow-down
        2
        ·
        edit-2
        3 days ago

        You walk over to it and make the change?

        How often do these freezers need changing of temperature? My guess would be at most a handful of times a year.

        Amd if the controls aren’t remotely connected you don’t have to worry about this type of issue.

        • plantfanatic@sh.itjust.works
          link
          fedilink
          English
          arrow-up
          2
          arrow-down
          3
          ·
          edit-2
          3 days ago

          So you pay to have someone stand around staring at a temp gauge all day? Yeah…. Sure buddy.

          And a delivery of new food, temp changes. Someone leaves a door open too long, run a chill cycle. That’s why the is stuff is automated. It’s so random. The temp and fan settings are changed probably a dozen times an hour. If it’s not, spoilage will happen.

          • crater2150@feddit.org
            link
            fedilink
            English
            arrow-up
            5
            arrow-down
            1
            ·
            3 days ago

            But that automation is so simple, it doesn’t need to connect to an external system. You set the target temperature once and the system regulates the cooling. No person needed, neither remote or in front of the thing.

            And temperature sensors are cheap. Just have one for the regulation, and a separate one for remote monitoring.

            • plantfanatic@sh.itjust.works
              link
              fedilink
              English
              arrow-up
              1
              arrow-down
              2
              ·
              edit-2
              3 days ago

              Than you don’t have the logging that is required for food safety and QC.

              So that one be hacked anyways and accomplish nothing?

          • hanke@feddit.nu
            link
            fedilink
            English
            arrow-up
            4
            arrow-down
            2
            ·
            3 days ago

            The whole point was keeping the temperature sensor readable remotely so that you didn’t have to pay someone to stand around all day.

            Absolute worst case, add a second temp sensor for the automated chill cycles. Pretty sure temperature sensors aren’t that expensive.

            • plantfanatic@sh.itjust.works
              link
              fedilink
              English
              arrow-up
              2
              arrow-down
              1
              ·
              edit-2
              3 days ago

              The whole point was keeping the temperature sensor readable remotely so that you didn’t have to pay someone to stand around all day.

              Yes? That was the problem with your suggesting someone go and change it. If you do that, and don’t have it automate the cooler, you STILL need someone.

              Absolute worst case, add a second temp sensor for the automated chill cycles. Pretty sure temperature sensors aren’t that expensive.

              So THAT one can be hacked anyways? Are you even thinking these solutions out at all? Like a little bit?

              • hanke@feddit.nu
                link
                fedilink
                English
                arrow-up
                2
                arrow-down
                1
                ·
                3 days ago

                I feel like you’re not understanding what I am trying to convey. Or I am not being clear enough?

                A temperature sensor being hacked is nothing to worry about. Worst case scenario, the hacked sensor will report the wrong temperature and some employee will come running over to the freezer. Upon manual inspection they will realise the temperature is in fact not +50°C despite the exposed sensor reporting that.

                The freezers automated freezing/heating just runs off an other separate temperature sensor that won’t be hacked since it is not exposed to the internet.

                Don’t this make sense to you? 😅

                • plantfanatic@sh.itjust.works
                  link
                  fedilink
                  English
                  arrow-up
                  1
                  arrow-down
                  2
                  ·
                  edit-2
                  3 days ago

                  Do you not realize all the stuff would be garbage anyways because the legal log says it got too hot? You have it automated so you can adjust or fix the issue before you just water an entire cooler of product lmfao.

                  You seem to not comprehend that you’re solutions accomplish literally nothing but more money and time for employees.